| Parameter | R-16KTL | |
|---|---|---|
| AC OUTPUT (LOAD) | ||
| Rated Output Power | 16000W | |
| Max. Peak Power | 32000VA | |
| Rated Output Voltage | 230/400Vac (Three-Phase) | |
| Load Motor Capacity | 10HP | |
| Rated Frequency | 50/60Hz ± 0.3Hz | |
| Waveform | Pure sine wave | |
| Switch Time | 10ms (Typical) | |
| AC OUTPUT (GRID) | ||
| Rated Output Power | 16000W | |
| Max. Apparent Power | 32000VA | |
| Power Factor | 0.8 leading to 0.8 lagging | |
| Rated Voltage | 3L/N/PE 230/400Vac | |
| Rated AC Frequency | 50/60Hz | |
| Rated Output Current | 23.2A | |
| THD | <3% | |
| BATTERY | ||
| Battery Type | Lithium-ion Battery / Lead-acid Battery / User-defined | |
| Rated Battery Voltage | 48Vdc | |
| Battery Voltage Range | 40~60Vdc | |
| Max. Grid Charging Current | 300Adc | |
| Max. Generator Charging Current | 300Adc | |
| Max. Hybrid Charging Current | 300Ad | |
| PV INPUT | ||
| No. of MPPT Trackers | 3 | |
| Max. PV Input Power | 24000W | |
| Max. PV Input Current | 26Adc / 26Adc / 26Adc | |
| Max. Short Circuit Current | 45Adc / 45Adc / 45Adc | |
| Max. Open Circuit Voltage | 1000Vdc | |
| MPPT Voltage Range | 160~800Vdc | |
| GRID/GENERATOR INPUT | ||
| Input Voltage Range | Phase Voltage: 170V~280V; Line Voltage: 305V~485V | |
| Input Frequency Range | 50Hz / 60Hz | |
| Bypass Overload Current | 70A | |
| EFFICIENCY | ||
| MPPT Tracking Efficiency | 99.9% | |
| Max. Efficiency | ≧97.8% | |
| European Efficiency | 97.2% | |
| GENERAL DATA | ||
| Parallel Capacity | 1~9 Units | |
| Dimensions | 800x470x313mm | |
| Weight | 59.5kg | |
| Protection Level | IP65 | |
| Temperature | -25 to +60℃, >45℃ Derate | |
| Warranty | 5 years | |
| Certificate | EN50549, VDE4105, IEC62109-1, IEC62109-2, EN61000-6-1, EN61000-6-3, FCC 15 class B, RoHS | |
| Humidity Range | 0~100% | |
| Cooling Method | Heat sink + intelligent fan cooling | |
| Noise | <55dB | |
| Communication Port | RS485 / CAN / USB / Dry contact | |
| External Module | WIFI / 4G Stick | |
| PROTECTION | ||
| Protection Features | PV lightning protection, anti-islanding protection, reverse connection protection for PV input, insulation resistance detection, leakage current detection, output overcurrent protection, output short-circuit protection | |
| Overvoltage Protection Level | AC type II/DC type III | |
| Surge Protection | AC type II/DC type II | |